Solutions To Common Faults Of Chillers
Usually in the process of operating the chiller, the more common faults are as follows:
Problem 1: Turn on the power switch but the power indicator light of the industrial chiller does not light up
1 The three-phase wiring of the power supply is wrong (pay attention to the auxiliary control line), check the wiring problem;
2 If the fuse is not installed, install an appropriate fuse;
3 The power indicator light is damaged, replace the electronic board.
Question 2: Turn on the power switch and the water pump switch to burn the fuse
1 Circuit short circuit fault check control wire and main power wire;
2. The water pump rotor is stuck, use a screwdriver to loosen the motor rotor (applicable to industrial chillers below 5 hp).
Problem 3: Compressor failure
1 The compressor coil is short, open circuit, replace the matching compressor;
2 The compressor overload protector will automatically trip, adjust the current limit of the protector appropriately within the allowable range and press the reset button.
Question 4: High Voltage Failure
1 Poor heat dissipation, the radiator is too dirty, clean the radiator;
2. Poor ventilation, improve ventilation conditions;
3. The cooling fan does not work, check whether the fan motor is burned out and short-circuit repair or replace the motor and motor high-voltage engine is damaged, replace the high-voltage engine;
4. If there is insufficient refrigerant in poor refrigeration or pipeline leakage, supplement refrigerant or repair welding after leak detection, and then add refrigerant after vacuuming;
5 Poor heat dissipation, the radiator is too dirty, the cooling water valve is not opened or opened too small, clean the radiator, and fully open the valve.
Problem five: water pump failure
1. The pump motor coil is short, open circuit, repair the motor coil or replace the motor;
2. The overload protector of the water pump will automatically trip, and the current limit of the protector will be appropriately increased within the allowable range, and the reset button will be pressed halfway.
Question 6: The temperature display number on the temperature press table jumps up and down
1 The temperature control meter is damaged, repair or replace the temperature control meter
2 The temperature sensing wire is in poor contact, repair or replace the temperature sensing wire
3 If the temperature sensing line and the temperature measuring body are dirty, wipe the temperature measuring body clean.
Problem 7: Compressor frost
1 If the circulating water is circulating or the valve is not opened, check the water valve and all pipelines to ensure smooth flow, and install short-circuit pipelines;
2 If the configuration of the circulating water pipe is too small, increase the diameter of the circulating water pipe to ensure normal water circulation.
Question 8: Freezing in the circulating water tank
1 The set temperature is too low to correct the set value
2 There is no circulating water in the water tank, and a circulating water circuit is short-circuited between the outlet and the inlet of the chilled water
3 The temperature control meter is out of control, replace the temperature control meter.